Working Space around Indoor Panel/Circuit Board (NES 312.2):
Voltage 
 | Exposed live parts to Not live parts( or grounded parts ) | Exposed live parts to Grounded parts (concrete, brick, and walls). | Exposed live parts on both sides | 
Up to 150 V 
 | 
0.914 Meter (3 Ft) 
 | 
0.914 Meter (3 Ft) 
 | 
0.914 Meter (3 Ft) 
 | 
150 V to 600 V 
 | 
0.914 Meter (3 Ft) 
 | 
1.07 Meter (3’6”) 
 | 
1.22 Meter (4 Ft) 
 | 
Clearance around an Indoor electrical panel (NES 110.26):
Description of Clearance 
 | 
Distance  (min) 
 | 
| Left to Right the minimum clearance | 
0.9 Meter (3 Ft) 
 | 
| Distance between Panel and wall | 
1.0 Meter 
 | 
| Distance between Panel and Ceiling | 
0.9 Meter 
 | 
| Clear Height in front of Panel>480V | 
2.0 Meter 
 | 
| Clear Height in front of Panel <480v span="span">480v> | 
0.9 Meter (3 Ft) 
 | 
| Clearance When Facing Other Electrical Panels < 480V | 
0.9 Meter (3 Ft) 
 | 
| The width of the workingspace in front of the Panel | 
The width of Panel or 0.762 Meter which is Greater. 
 | 
| Headroom of working spaces for panel boards (Up to 200Amp) | 
Up to 2 Meter 
 | 
| Headroom of working spaces for panel boards (More than 200Amp &Panel height is max 2 Meter) | 
Up to 2 Meter( If Panel height is max 2 Meter) 
 | 
| Headroom of working spaces for panel boards (More than 200Amp &Panel height is more than 2 Meter) | 
If Panel height is more than 2 Meter than clearance should not less than panel Height 
 | 
| Entrance For Panel (More than 1200 Amp and over 1.8 m Wide) | 
One entrance required for working space (Not less than 610 mm wide and 2.0 m high ) 
 | 
| Personal Door For Panel (More than 1200 Amp) | 
Personnel door(s) intended for entrance to and egress from the working space less than 7.6 m from the nearest edge of the working space 
 | 
| Dedicated Electrical Space. | 
Required Space is width and depth of the Panel and extending from the floor to a height of 1.8 m (6 ft) above the equipment or to the structural ceiling, whichever is lower 
 | 
| The door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates, or other devices that are normally latched but open under simple pressure | |
| the work space shall permit at least a 90 degree opening of equipment doors or hinged panels | 
Clearance for Conductor Entering in Panel (NES 408.5):
Description of Clearance 
 | Distance (min) | 
Spacing between The conduit 
or raceways(including their end fittings) and Bottom of Enclosure 
 | 
Not rise more than 75 mm (3 in) above the bottom of the enclosure 
 | 
Spacing Between Bottom 
of Enclosure and Insulated bus bars, their supports, 
 | 
200 mm 
 | 
Spacing Between Bottom of Enclosure and Non insulated bus bars 
 | 
200 mm 
 | 
Clearance between Bare Metal Bus bar in Panel (NES 408.5):
Voltage 
 | Opposite PolarityMounted on Same 
Surface 
 | Opposite PolarityWhere Held Free in Air | Live Parts to Ground | 
| Up to 125 V | 19.1 mm | 12.7 mm | 12.7 mm | 
| 125 V to 250 V | 31.8 mm | 19.1 mm | 12.7 mm | 
| 250 V to 600 V | 50.8 mm | 25.4 mm | 25.4 mm | 
Clearance of Outdoor electrical panel to Fence/Wall (NES 110.31):
Voltage 
 | Distance (min) | 
| 600 V to 13.8 KV | 
3.05 Meter 
 | 
| 13.8 K V to 230 KV | 
4.57 Meter 
 | 
| Above 230 KV | 
5.49 Meter 
 | 
Working Space around Indoor Panel/Circuit Board (NES 110.34):
Voltage 
 | Exposed live parts to Not live parts( or grounded parts ) | Exposed live parts to Grounded parts (concrete, brick, and walls). | Exposed live parts on both sides | 
601 V to 2.5 K V 
 | 
0.914 Meter (3 Ft) 
 | 
1.2 Meter (4 Ft) 
 | 
1.5 Meter (5 Ft) 
 | 
2.5 K V to 9.0 K V 
 | 
1.2 Meter (4 Ft) 
 | 
1.5 Meter (5 Ft) 
 | 
1.8 Meter (6 Ft) 
 | 
| 9.0 K V to 25 K V | 
1.5 Meter (5 Ft) 
 | 
1.8 Meter (6 Ft) 
 | 
2.5 Meter (8 Ft) 
 | 
| 25 K V to 75 K V | 
1.8 Meter (6 Ft) 
 | 
2.5 Meter (8 Ft) 
 | 
3.0 Meter (10 Ft) 
 | 
Above 75 KV 
 | 
2.5 Meter (8 Ft) 
 | 
3.0 Meter (10 Ft) 
 | 
3.7 Meter (12 Ft) 
 | 
Clearance around an Outdoor electrical panel (NES 110.31):
Description of Clearance 
 | Distance (min) | 
| Clear work space: | Not less than 2.0 Meter high(Measured vertically from the floor or platform) or not less than 914 mm (3 ft) wide (Measured parallel to the equipment). | 
| Entrance For Panel (More than 1200 Amp and over 1.8 m Wide) | One entrance required for working space (Not less than 610 mm wide and 2.0 m high ) | 
| Entrance For Panel: On Large panels exceeding 1.8 Meter in width | One Entrance at each end of the equipment. | 
| Nonmetallic or Metal-enclosed Panel in general public and the bottom of the enclosure is less than 2.5 m (8 ft) above the floor or grade level | Enclosure door or hinged cover shall be kept locked. | 
Elevation of Unguarded Live Parts above Working Space (NES 110.34E):
Voltage 
 | Elevation (min) | 
| 600 V to 7.5 KV | 
2.8 Meter 
 | 
| 7.5 K V to 35 KV | 
2.9 Meter 
 | 
| Above 35 KV | 
2.9 Meter + 9.5 mm/KV 
 | 
Working Space for Panel (Code Georgia Power Company):
Voltage 
 | Exposed live parts to Not live parts( or grounded parts ) | Exposed live parts to Grounded parts (concrete, brick, and walls). | Exposed live parts on both sides | 
Up to 150 V 
 | 
3.0 Meter 
 | 3.0 Meter | 3.0 Meter | 
150 V to 600 V 
 | 3.0 Meter | 3.5 Meter | 4.0 Meter | 
600 V to 2.5 KV 
 | 3.0 Meter | 4.0 Meter | 5.0 Meter | 
2.5 KV to 9 KV 
 | 3.0 Meter | 5.0 Meter | 6.0 Meter | 
9 KV to 25 KV 
 | 5.0 Meter | 6.0 Meter | 6.0 Meter | 